Input DescriptionΒΆ

../_images/c2d27c77e38a2f400a33139000eba54e1

EN

Data_Type Default_Value Range Unit
BOOL FALSE TRUE/FALSE -

The input EN has to be driven in level triggered mode.

In order to enable the execution of the Function Block the input EN has to be set to value TRUE. It keeps on executing until the input EN is set back to value FALSE.

While it is executed its inputs are continuously evaluated.

Mode

Data_Type Default_Value Range Unit
WORD - - -

Access control for the LED:

MODE = 0 = runtime system

MODE = 1 = user program

LED

Data_Type Default_Value Range Unit
WORD - - -

Input LED is used to specify the LED:

CM574:

1 : RUN LED

2 : ERROR LED

3 : COM1 Status LED

4 : COM2 Status LED

5 : READY LED

6 : STAT LED

PM57x, PM58x, PM59x:

1 : RUN LED

2 : ERROR LED

Eco:

1 : RUN LED

2 : ERROR LED

3 : COM1 Status LED

PM595:

1 : RUN LED (green only)

2 : ERROR LED (red only)

3 : CAN LED (green/red/orange)

8 : Batt State LED (green/red/orange)

9 : Function 1 LED (green/red/orange)

10 : Function 2 LED (green/red/orange)

11 : Function 3 LED (green/red/orange)

12 : Function 4 LED (green/red/orange)

13 : Function 5 LED (green/red/orange)

VALUE

Data_Type Default_Value Range Unit
WORD - - -

Input VALUE is used to specify the static value of the LED. Only applicable if the LED is not in mode = 0.

Following values are possible:

0 = LED off

1 = LED on (Default colour used if applicable)

2 = LED on, green (only at PM595)

3 = LED on, red (only at PM595)

4 = LED on, orange (only at PM595)

PERIOD

Data_Type Default_Value Range Unit
DWORD - - ms

Input PERIOD is used to set the blinking period of the LED in ms.