PUMP_BOOST_CTRL_VISU_PH

Visualization Faceplate for the Function Block PUMP_BOOST_CTRL.

../_images/92ba8af91260fc570a33139001c0eb27
Colors of the variables
Color Meaning
white Actual FALSE and should be FALSE in normal operation
green Actual TRUE and should be TRUE in normal operation
yellow Actual FALSE but should be TRUE in normal operation
red Actual TRUE but should be FALSE in normal operation
Visualization parameters
Variable element Access Way of access Description (all elements refer to the Function Block instance, replaced for the placeholder $FB$)
EN R/W Toggle To enable the Function Block with the true value.
START R/W Toggle To start the Boost control functionality.
OP_MODE R/W Numpad – value 0 to 2 Operation mode of the station, 0= single pump, 1=traditional pump, 2=multi pump.
MASTER_LOC R/W Numpad – value 0 to 1

Defines the master location.

INSTART: youngest pump in the network is the master.

1- STABLE: master is always fixed.

START_SPEED_SLV_1 R/W Numpad- value 0 onwards Speed of master in RPM at which the follower pump 1 starts.
START_SPEED_SLV_2 R/W Numpad- value 0 onwards Speed of master in RPM at which the follower pump 2 starts.
STOP_SPEED_SLV_1 R/W Numpad- value 0 onwards Speed of master in RPM at which the follower pump 1 stops.
STOP_SPEED_SLV_2 R/W Numpad- value 0 onwards Speed of master in RPM at which the follower pump 2 stops.
START_DELAY R/W Numpad- value 0 onwards Time delay in seconds for starting the pump.
STOP_DELAY R/W Numpad- value 0 onwards Time delay in seconds for stopping the pump.
DONE R   Execution finished when output DONE = TRUE.
ERR R   Error occurred during execution when output ERR = TRUE.
ENO R   Error code.