PUMP_INTERFACE_VISU_PH
Visualization Faceplate for the Function Block PUMP_INTERFACE.
Colors of the variables
Color |
Meaning |
white |
Actual FALSE and should be FALSE in normal operation |
green |
Actual TRUE and should be TRUE in normal operation |
yellow |
Actual FALSE but should be TRUE in normal operation |
red |
Actual TRUE but should be FALSE in normal operation |
Visualization parameters
Variable element |
Access |
Way of access |
Description (all elements refer to the Function Block instance, replaced for the placeholder $FB$) |
EN |
R/W |
Toggle |
To enable the Function Block with the true value. |
PUMP_ID |
R/W |
Numpad – value 1 to 3 |
To enter the ID of the pump. |
PRIORITY |
R/W |
Numpad – value 1 to 3 |
To enter the priority of the pump. |
PUMP_ON |
R/W |
Toggle |
To switch off/On the pump individually. For the FALSE value the user can remove this pump from the network in case of any problem/fault. |
PUMP_NOMINAL_SPEED |
R/W |
Numpad – value 0 onwards |
To enter the nominal speed of the pump motor. |
FOLLOWER_MODE |
R/W |
Numpad – value 0 to 2 |
Follower mode to decide at what speed the follower pumps must move. 0= Fixed, 1=copy master, 2=master speed. |
FOLLOWER_REF |
R/W |
Numpad – value 0 onwards |
follower speed reference in RPM, when FOLLOWER_MODE =0, i.e. fixed. |
PUMP_READY |
R/W |
Toggle |
Input to attach the ready status of the drive of the pump. |
PUMP_OPERATING |
R/W |
Toggle |
Input to attach the operating status of the drive of the pump. |
PUMP_TRIPPRED |
R/W |
Toggle |
Input to attach the fault status of the drive of the pump. |
PUMP_RUNTIME_RESET |
R/W |
Toggle |
TRUE value of this variable resets the actual runtime to Zero value. |
DONE |
R |
|
Execution finished when output DONE = TRUE. |
ERR |
R |
|
Error occurred during execution when output ERR = TRUE. |
ENO |
R |
|
Error code. |
PUMP_START |
R |
|
On command to the pump. |
PUMP_REF |
R |
|
Speed reference to the pump in RPM. |
PUMP_REF_FB |
R |
|
Field bus speed reference to the pump in the range of -20000 to 20000. |
PUMP_RUNTIME |
R |
|
Actual runtime of the pump. |