Input Description

../_images/a0911bcee389c7990a33139000eba54e

FREI

Data_Type Default_Value Range Unit
BOOL - - -

Processing of the Function Block is controlled via input FREI.

FREI = FALSE:

All Function Block outputs are set to the value “FALSE”. However, this is not valid, if a job is currently being processed, i. e. processing of a job which is currently being processed, is not affected by FREI = FALSE.

FREI = FALSE/TRUE edge:

Processing of the job is enabled. Input FREI is no longer evaluated during processing of the job.

FREI = TRUE:

The Function Block is not processed, i. e. it no longer changes its outputs. However, this is not valid, if a job is currently being processed.

SLOT

Data_Type Default_Value Range Unit
BYTE - - -

Reserved for future extensions.

COM

Data_Type Default_Value Range Unit
BYTE - - -

Communication Port to which the CS31 Bus Module is connected.

GRN

Data_Type Default_Value Range Unit
BYTE - 0 … 63 -

Group number with which the remote module is addressed by the PLC program.

Example:

On binary input E 12,08, “12” is the group number and “08” is the channel number.

CODE

Data_Type Default_Value Range Unit
BYTE - - -

The identification of the job to be executed is specified at input CODE <no title>.

D1…D8

Data_Type Default_Value Range Unit
BYTE - - -

The parameters required for the job are preset at the inputs D1 … D8. The number of parameters depends on the job to be executed. There are also jobs requiring no parameters <no title>.