Adjustment of Parameters for Drive

The drive has to be adjusted to use the ABBdrive profile. To do this, and to establish the PROFIBUS connection to the PLC you have to follow the according documentation. In addition, some parameters have to be adjusted. These are listed in the following tables. For further commissioning, follow the chapter “Start-Up” in the drives manual.

Parameter Adjustment for ACS35x
START/STOP        
Parameter Name Value Mnemonic Comment
10.1 EXT1 START FUNC 10 KOMM Fieldbus Interface
11.2 EXT1/EXT2 0 EXT1 FBA, 2.12 FBA MAIN CW
11.3 AUSW.EXT SOLLW1 8 KOMM  
16.1 FREIGABE 8 KOMM  
16.4 FEHL QUIT 8 KOMM  
22.1 BE/VERZ 1/2 AUSW 0 False Select 22.02..22.04
Parameter Adjustment for ACS35x
FIELDBUS        
FBA Settings        
Parameter Name Value Mnemonic  
51.01 FBA TYPE 1   =PROFIBUS DP Displays the type of the fieldbus adapter module.
51.02 NODE ADDRESS     According to PLC configuration.
51.03 BAUDRATE     According to PLC configuration.
51.04 TELEGRAM TYPE 2   (= PPO2) Displays telegram type selected by PLC configuration tool.
51.05 PROFILE 1   (= ABB drive)
Parameter Adjustment for ACS35x
FIELDBUS        
FBA Data In        
Parameter Name Value Mnemonic  
54.01 FBA DATA IN1 4   Status word
54.02 FBA DATA IN2 5   Actual value 1
54.03 FBA DATA IN3 401   Actual fault
54.04 FBA DATA IN4      
54.05 FBA DATA IN5      
54.06 FBA DATA IN6      
Parameter Adjustment for ACS35x
FIELDBUS        
FBA Data Out        
Parameter Name Value Mnemonic  
55.01 FBA DATA OUT2 1   Control word
55.02 FBA DATA OUT3 2   Reference 1
55.03 FBA DATA OUT4 2202   Acceleration
55.04 FBA DATA OUT5 2203   Deceleration
55.05 FBA DATA OUT6      
55.06        
Parameter Adjustment for ACS35x
FIELDBUS        
Options        
Parameter Name Value Mnemonic Comment
98.02 Comm Prot Sel 2 EXT FBA Select of external fieldbus adapter