5000hex…5FFFhex - Request Error¶
DEC | HEX | Error description |
---|---|---|
20482 | 5002 | The request is not supported (e.g. in the simulation mode of the Control Builder). |
20485 | 5005 | Invalid internal state -> function block probably called in invalid manner/sequence |
20499 | 5013 | Timeout error ECAT_COE_READ, ECAT_COE_Write: Request timeout occurs |
20503 | 5017 | Incorrect length ARC..: Invalid data length CAN2..: Invalid DLC in message ETH_UDP..: Invalid data length ECAT_COE_READ, ECAT_COE_Write: Request/ Response length invalid |
20504 | 5018 | Traceability data is corrupted. |
20507 | 501B | Access error COM_MOD_MAST: Invalid memory address DATA or DATA + NB. At least one datum is outside of the access range of the user program. The range includes different flag ranges. ETH_MOD_MAST: Invalid memory address DATA or DATA + NB. At least one datum is outside of the access range of the user program. The range includes different flag ranges. |
20508 | 501C | Invalid number (quantity) CAN2A_SEND: Invalid number of messages at input NUM COM_MOD_MAST: Invalid number of data at NB (0 or more than permitted). ETH_MOD_MAST: Invalid number of data at NB (0 or more than permitted).20515 |
20513 | 5021 | IO_PROD_ENTRY_READ: I/O Module not found: input MODULE invalid |
20515 | 5023 | Failed to read traceability data from I/O Module. |
20517 | 5025 | Address error ARC..: Invalid IP address CAN2..: Invalid identifier in message COM_MOD_MAST: Invalid slave address. Broadcast not permitted in connection with the selected function code. ETH_MOD_MAST: Invalid slave address. Broadcast not permitted in connection with the selected function code. ETH_UDP..: Invalid IP address. |
20518 | 5026 | Function error COM_MOD_MAST: Invalid function code FCT. ETH_MOD_MAST: Invalid function code FCT. |
20735 | 50FF | DIAG..: Simulation mode |
24575 | 5FFF | Operation pending / busy -> wait and try again later |