7000hex…7FFFhex - Product Libraries

Dec Hex Library Error description
28672 7000 Drives Any activity was NOT completed within an appropiate TIME
28673 7001 Read or write parameter could not be completed
28674 7002 A parameter at the Function Block is out of the possible range. This does not refer to the parameter range which is allowed for the drive but just to the 32 bits integer which is used for internal calculation
28675 7003 The field bus connection is faulty
28677 7005 Wrong PPO type
28678 7006 Wrong or no adapter type could be detected
28679 7007 Drive type does not match to Function Block
28680 7008 Function aborted
28681 7009 Error while reading scaling parameter for REF1
28682 700A Wrong parameter number at read/write parameter
28683 700B COM interface differs from others on same LINE_TOKEN variable
28684 700C Profile type error
28685 700D Function Block Read_Parameters has been executed with error
28686 700E Function Block Write_Parameters has been executed with error
28687 700F No connection to communication block, or error in communication block
28688 7010 Error at reading the drives communication profile value
28689 7011 Drive communication profile can not be used with this Function Block
28690 7012 PROFINET or PROFIBUS write packet size exceed 240 byte data limit
28928 7100 Solar ALARM: Limit exceeded. System has moved more than POS_DEG_LIMIT distance without any moving command.
28929 7101 ALARM: Timeout. The system has not reached POS_DEG_LIMIT within the tolerance time (3 * t POS_TIME_LIMIT [ms]).
28930 7102 ALARM: Limit at wrong side reached. System has reached POS_DEG_LIMIT distance in the opposite DIR to actual movement order.
28931 7103 ALARM: Low Limit exceeded. Tracker position is less than VIRTUAL_LIMIT_MIN.
28932 7104 High Limit exceeded. Tracker position is more than VIRTUAL_LIMIT_MAX.
28933 7105 Warning: Interlocking. Try to move BACKWARD while STOP_BWD input is set.
28934 7106 Warning: Interlocking. Try to move FORWARD while STOP_FWD input is set.
28935 7107 Warning: Interlocking. Both STOP_BWD and STOP_FWD input are set.
29184 7200 Data Logger zLOG_ERROR_NO_TYPE_SPECIFIED
29185 7201 zLOG_ERROR_LENGTH_BOOL_EXCEEDED
29186 7202 zLOG_ERROR_LENGTH_BYTE_EXCEEDED
29187 7203 zLOG_ERROR_LENGTH_INT_EXCEEDED
29188 7204 zLOG_ERROR_LENGTH_WORD_EXCEEDED
29189 7205 zLOG_ERROR_LENGTH_DINT_EXCEEDED
29190 7206 zLOG_ERROR_LENGTH_DWORD_EXCEEDED
29191 7207 zLOG_ERROR_LENGTH_REAL_EXCEEDED
29195 720B zLOG_ERROR_OPEN_ERR
29196 720C zLOG_ERROR_GETPOS_ERR
29197 720D zLOG_ERROR_SETPOS_ERR
29198 720E zLOG_ERROR_WRITE_ERR
29199 720F zLOG_ERROR_READ_ERR
29200 7210 zLOG_ERROR_CLOSE_ERR
29201 7211 zLOG_ERROR_GETSIZE_ERR
29202 7212 zLOG_ERROR_FLUSH_ERR
29205 7215 zLOG_ERROR_MAX_NUMBER_OF_FILES_EXCEEDED
29206 7216 zLOG_ERROR_MAX_NUMBER_OF_DATASETS_PRO_FILE
29207 7217 EXCEEDED zLOG_ERROR_FILE_WRITE_FAILED
29208 7218 zLOG_ERROR_FILE_READ_FAILED
29210 721A zLOG_ERROR_CREATE_DIRECTORY
29211 721B zLOG_ERROR_FILE_MOVE
29212 721C zLOG_ERROR_NO_CSV_FOUND_IN_DATASET
29213 721D zLOG_ERROR_DELETE_ACTUAL_FILE
29214 721E zLOG_ERROR_FORMAT_DISK1
29215 721F zLOG_ERROR_FORMAT_DISK2
29216 7220 zLOG_ERROR_DELETE_ACTUAL_FILES_NO_FILE_FOUND
29217 7221 zLOG_ERROR_DELETE_SAVE_FILES_NO_FILE_FOUND
29218 7222 zLOG_ERROR_ILLEGAL_MODE
29219 7223 zLOG_ERROR_ILLEGAL_DESIGNATION_ON_DISK1
29220 7224 zLOG_ERROR_ILLEGAL_DESIGNATION_ON_DISK2
29221 7225 zLOG_ERROR_FORMAT_NOT_SUPPORTED
29222 7226 zLOG_ERROR_MODE3_AND_DISK2_EXTENTION_TRUE_NOT_ALLOWED
29230 722E zLOG_ERROR_29230_TIMEOUT_DIRECTORY_CREATE_FILE_MOVE
29231 722F zLOG_ERROR_RESERVE
29232 7230 zLOG_ERROR_TIMEOUT_DISK_FORMAT
29233 7231 zLOG_ERROR_TIMEOUT_FILE_DELETE
29234 7232 zLOG_ERROR_TIMEOUT_WRITE_DATASET_IN_FILE
29235 7233 zLOG_ERROR_TIMEOUT_READ_DATASET_IN_CASE_OF_CONNECT
29236 7234 zLOG_ERROR_TIMEOUT_WRITE_DATASET_IN_CASE_OF_CONNECT
29237 7235 zLOG_ERROR_TIMEOUT_READ_DATASET_IN_CASE_OF_NOT_CONNECT
29238 7236 zLOG_ERROR_TIMEOUT_IEC60870_COMMUNICATION
29312 7280 Temperature Control

Fault (TuneFault): “Tuning failed”: outputs disabled, see Tune_Status

Remedy: Check for tune set point and currrent temperatur

29313 7281

Fault (TC_Fault_1): “Bad Thermocouple reading”: outputs disabled.

Remedy: Bad Thermocouple reading: outputs disabled

29314 7282

Fault (TC_Fault_2): “Plausibility check not passed”: outputs disabled.

Remedy: Check for inverted connection of Thermocouple.

29315 7283

Fault (HighHighTempFalt): “HighHigh temperature alarm”: outputs disabled.

Remedy

  • Check for defective cooling device.
  • Check for correct setting of HIGHHIGH_TEMP and SET_TEMP.
29316 7284

Fault (LowLowTempFault): “LowLow temperature alarm”: outputs disabled.

Remedy

  • Check for defective heating device.
  • Check for correct setting of LOWLOW_TEMP and SET_TEMP.
29319 7287 High temperature alarm
29320 7288 Low temperature alarm
29321 7289 High deviation alarm
29330 7292 Zone_size and zone_index are not assigned
29335 7297 No Group Function Block call possible: internal Group function call for TECT_TEMP_CONTROL or TECT_PWM8 failed.
29336 7298 TimeOut of one operation state.
29337 7299 Read data failed: no correct format of data items.
29322 728A Low deviation alarm
29323 728B

Fault: (NoHighHighLowLow): “No plausible HighHigh or LowLow limit is defined”

Remedy: Check the HighHighTemp and low low temp.

29324 728C

Fault (WrongLimits): “No plausible wrong limits defined”

Remedy: Check the defined limits.

29325 728D Heat and Cool are not enabled: Monitoring only.
29326 728E

Faut (NoAutoTune): “AutoTune cannot be started”

Remedy: Process in Manual mode or Heat is not enabled

29327 728F

Fault (NoPIDProcess): “PID process cannot be started”

Remedy: Process in Manual mode or no KS, TU, TG parameters are accepted.

29328 7290

Fault (Improper setting of HigHigh and High): HighHigh and High limits are not set correctly. Values are not taken by process/ADR_ZONEDATA.

Remedy: Check parameter settings.

29329 7291

Fault (Improper setting of LowLow and Low ): LowLow and Low limits are not set correct. Values are not taken by process/ADR_ZONEDATA.

Remedy: Check parameter settings.

29330 7292

Fault (No assignment for zone index and size): Zone_size and zone_index are not assigned.

Remedy: Check parameter settings.

29335 7297 Fault (No Group function possible):no Group Function Block call possible: internal Group function call for TECT_TEMP_CONTROL or TECT_PWM8 failed.
29336 7298 TimeOut of one operation state.
29337 7299

Fault (Reading failed):Read data failed: no correct format of data items.

Remedy: Check parameter settings.

29338 729A Fault (Incomplete log saving): Restart of the EN is required since last log saving is not complete
29339 729B

Fault (Less zone data available in RECIPE file than requested):Mismatch in number of zones declared and zone data in recipe.

Remedy: Check the zone data in CSV file and Num_of_zones declared in RECIPE.

29440 7300 CMS/(FM502 Invalid file format.
29445 7305 Number of channels > 1, not supported by this version of library.
29440 7300 Invalid RIFF Chunk ID
29441 7301 Invalid WAV Chunk ID
29442 7302 Invalid FMT Chunk ID
29443 7303 Invalid DATA Chunk ID
29444 7304 Invalid LABL Chunk ID
29445 7305 Number of channels >1 , not supported by this version of library.
29504 7340 No Channel activated
29505 7341 Internal Error (Start)
29506 7342 Internal Error (Poll)
29507 7343 Internal Error (Finish)
29508 7344 Not possible because of measurement running
29519 734F No Measurement possible. Device in Failure Loop.
29520 7350 Comunication Timeout to FM502
29521 7351 Internal File Error
29522 7352 Plausibility Check of Configuration wrong
29569 7381 Error in memory allocation to the input signal, due to insufficient memory available.
29571 7383 Wrong intermediate variable value
29572 7384 Error during reading wave file - check wave file for format compatibility.
29573 7385 Could not open indicated wave file.