Complete Error List of the S500 I/O Modules

E1..E4 d1 d2 d3 d4 Identifier 000…063 AC500 display <- displayed in 5)
Class Comp Dev Mod Ch Err PS501 PLC Browser
Byte 6 Bit 6..7 - Byte 3 Byte 4 Byte 5

Byte 6

Bit 0..5

FBP diagnosis block
Class Interface Device Module Channel Error identifier Error message Remedy Online number Online text
  1) 2) 3) 4)    
Errors of the S500 I/O Modules
S500 I/O Module errors
Light errors
3 14 1..10 1 0..7 4 Measurement overflow at the I/O module Check channel wiring and sensor power supply 234881028 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549380 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
3 14 1..10 31 31 3 Timeout in the I/O Module Replace I/O module 234946499 E3: I/O-Bus, Mod. [1..10]
11 / 12 ADR 1..10 184549379 E3: COM [1|2] [PROTOCOL] [ADR], [1..10], (>=)31
3 14 1..10 31 31 9 Overflow diagnosis buffer Restart 234946505 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549385 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (>=)31
3 14 1..10 31 31 10 Process voltage too high Check process voltage 234946506 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 11 Process voltage too low Check process voltage 234946507 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549387 E3: COM [1|2] [PROTOCOL] [ADR] [1.. 10], (>=) 31
3 14 1..10 31 31 18 Plausibility check failed (iParameter) Check configuration 234946514 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 19 Checksum error in the I/O Module

Non-safety I/O: Replace I/O Module

Safety-I/O: Check safety configuration and CRCs for iParameters and F-Parameters

234946515 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549395 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (³) 31
3 14 1..10 31 31 20 PROFIsafe communication error Restart I/O Module. If this error persists, contact ABB technical support. 234946516 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 25 PROFIsafe watchdog timed out Restart I/O Module. If this error persists, increase PROFIsafe watchdog time. 234946521 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 26 Parameter value Check master or configuration 234946522 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549402 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (³)31
3 14 1..10 31 31 28 F-Parameter configuration and address switch value do not match Check I/O Module’s F-Parameter configuration and module address switch value 234946524 E3: I/O-Bus, Mod. 1..10
1..4 ADR 1..10    
3 14 1..10 31 31 36 Internal data interchange disturbed Replace I/O Module 234946532 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549412 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (³)31
3 14 1..10 31 31 40 Different hardware and firmware versions in the module Replace I/O Module 234946536 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549416 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (³)31
3 14 1..10 31 31 43 Internal error in the device Replace I/O Module 234946539 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549419 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (³)31
3 14 1..10 31 31 47 Sensor voltage too low Check sensor voltage 234946543 E3: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549423 E3: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (³)31
Warnings
4 14 1..10 31 31 45

Process voltage switched off

(ON->OFF)

Process voltage ON 234946541 E4: I/O-Bus, Mod. [1.. 10]
11 / 12 ADR 1..10 184549421 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], (³)31
Channel errors of the S500 I/O modules
Warnings
4 14 1..10 1 0..7 1 Wrong measurement; wrong temperature at the compensations channel Check temperature compensation channel 234881025 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549376 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 2

AI531: Wrong measurement; potential difference is to high

CD522: PWM duty cycle out of duty area

AI531: Check potential difference

CD522: Check min/max values

234881026 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549378 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 4 Measurement overflow at the I/O module Check channel wiring and sensor power supply 234881028 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549380 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 7 Measurement underflow at the analog input Check input value 234881031 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549383 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 4 1..10 1 0..7 10 Input/output value to high Check input/output value 234881034 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549386 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 11

AI531:Output voltage 10 V to small

CD522: Output voltage 5 V to small (sensor)

AI531: Check charge of the output voltage

CD522: Check connection

234881035 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549387 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 18 Internal fuse to 0 V blown, 0 V not connected to ZP Replace I/O Module 234881042 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 /12 ADR 1..10 184549394 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 1 0..7 47 Short-circuit at the analog input Check terminal 234881071 E4: I/O-Bus, Mod. [1.. 10], 1, [0..7]
11 / 12 ADR 1..10 184549423 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10, [0..7]
4 14 1..10 1 0..7 48 Measurement overflow or cut wire at the analog input Check input value and terminal 234881072 E4: I/O-Bus, Mod. [1..7], 1, [0..7]
11 / 12 ADR 1..10 184549424 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 2 0..23 47 Short-circuit at the digital output Check terminal 234881071 E4: I/O-Bus, Mod. [1.. 10], 2, [0..7]
11 / 12 ADR 1..10 184549423 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 3 0..7 48 Measurement overflow at the analog output Check output value 234881072 E4: I/O-Bus, Mod. [1.. 10], 3, [0..7]
11 / 12 ADR 1..10 184549424 E4: COM [1|2] [PROTOCOL] [ADR], [1.. 10], [0..7]
4 14 1..10 3 0..7 7 Measurement underflow at the analog output Check output value 234881031 E4: I/O-Bus, Mod. [1.. 10], 3, [0..7]
Module errors DC551-CS31 and CI590
Light errors
3 11 ADR 31 31 3 Timeout in the I/O Module Replace I/O Module 184614851 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 9 Overflow of diagnosis buffer Restart 184614857 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 11 Process voltage too low Check process voltage 184614859 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 1..7 31 17 No communication with the I/O Module Replace I/O Module 184549393 E3: COM1 [PROTOCOL] [ADR], [1..7], (³)31
3 11 ADR 31 31 19 Checksum error in the I/O Module Replace I/O Module 184614867 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 26 Parameter error Check master 184614874 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 28 Configuration of PLC 1 and PLC 2 are different Check PLC CS31 Module configuration 184614876 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 36 Internal data interchange disturbed Check PLC program 184614884 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 40 Different hardware and firmware versions in the module Replace I/O Module 184614888 E3: COM1 [PROTOCOL] [ADR]
3 11 ADR 31 31 43 Internal error in the module Replace I/O Module 184614891 E3: COM1 [PROTOCOL] [ADR]
Warnings
4 11 ADR 31 31 33 PLC conflict *1 Check PLC program 184614881 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 34 Outputs are different (synchronization error) *2 Check PLC program and synchronize 184614882 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 45 Process voltage ON/OFF Process voltage ON 184614893 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 32 Wrong I/O Module on the slot Replace I/O Module and check configuration 184614882 E4: COM1 [PROTOCOL] [ADR], [1..7], (³)31
1..10 184549410 E4: COM1 [PROTOCOL] [ADR]
4 11 ADR 31 31 34 No response during initialization of the I/O Module Replace I/O Module 184614880 E4: COM1 [PROTOCOL] [ADR]
1..10 184549408 E4: COM1 [PROTOCOL] [ADR], [1..7], (³)31

1) FB HA control mode is both primary or both secondary. Could be only an error output of FB if too much diagnosis

2) if no other error occurs, the programs are not identical and parameter is set to report an error in this case

Channel errors DC551-CS31 and CI590
Warnings
4 11 ADR 31/1..10 8..23 47 Short-circuit at the digital output Check terminal 184549423 E4: COM1 [PROTOCOL] [ADR] E4: COM1 [PROTOCOL] [ADR], [1..7], (³)31
4 11 ADR 31/1..10 8..23 7 Measurement underflow at the analog in/output Check value 1846133383 E4: COM1 [PRO- TOCOL ] [ADR] E4: COM1 [PRO- TOCOL ] [ADR], [1..7], (³)31
Module errors DC505-FBP
Light errors
3 - 1..7 31 31 11 Process voltage too low Check process voltage    
3 - 1..7 31 31 17 No communication with the I/O module Replace I/O Module    
3 - 31 31 31 3 Timeout in the I/O module    
3 - 31 31 31 9 Overflow of diagnosis buffer Restart    
3 - 31 31 31 19 Checksum error in the I/O module Replace I/O Module    
3 - 31 31 31 26 Parameter error Check master    
3 - 31 31 31 36 Internal data interchange disturbed Replace I/O Module    
3 - 31 31 31 40 Different hardware and firmware versions in the module    
3 - 31 31 31 43 Internal error in the module    
Warnings
4 - 31 31 31 45 Process voltage ON/OFF Process voltage ON    
4 - 31/1..7 31 31 32 Wrong I/O Module on the slot Replace I/O Module and check configuration    
4 - 31/1..7 31 31 34 No response during initialization of the I/O module Replace I/O Module    
Channel errors DC505-FBP
Warnings
4 - 31 2 8..15 47 Short-circuit at the digital output Check terminal    
Parameter errors
Light errors
3 14 1..10 31 3 1 Wrong parameter value Check configuration 234944705  
3 14 1..10 31 3 28 F-Parameter configuration and address switch value do not match Check I/O Module F-Parameter configuration and module address switch value 234944732 E3: I/O-Bus, Mod. 1
3 14 1..10 31 3 19 Checksum error has occured in iParameter or F-Parameters Check safety configuration and CRCs for iParameter and F-Parameters 234944723 E3: I/O-Bus, Mod. 1
Runtime errors
Light errors
3 14 1..10 31 2 3 PROFIsafe watchdog timed out Restart I/O Module. If this error persists, increase PROFIsafe watchdog time 234944643 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 19 Checksum error has occured in iParameters Restart I/O Module. If this error persists, replace I/O module. Contact ABB technical support 234944659 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 20 PROFIsafe communication error Restart I/O Module. If this error persists, contact ABB technical support 234944660 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 28 Internal error Contact ABB technical support. Replace I/O Module 234944668 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 43 Internal runtime error in I/O module Contact ABB technical support. Replace I/O module 234944683 E3: I/O-Bus, Mod. 1
Background test errors
Light errors
3 14 1..10 31 2 4 I/O Module overvoltage Check I/O module power supply 234944644 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 7 I/O Module undervoltage Check I/O module power supply 234944647 E3: I/O-Bus, Mod. 1
3 14 1..10 31 2 18 Internal error Restart I/O module. If this error persists, replace I/O module. Contact ABB technical support 234944658 E3: I/O-Bus, Mod. 1
Specific errors AI, DI and DO
Light errors
3 14 1..10 0 0..15 3 Discrepancy time expired Check discrepancy time value, channel wiring and sensor 234881027 E3: I/O-Bus, Mod. 1-10, 0, 0-15
3 14 1..10 0 0..15 12

Module 0:

Test pulse error

Check wiring and sensor 234881036 E3: I/O-Bus, Mod. 1-10, 0, 0-15
2 0..8

Module 2:

Channel stuck-at error

Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. E3: I/O-Bus, Mod. 1..10, 2, 0..8
3 14 1..10 0 0..15 13

Module 0:

Channel test pulse cross-talk error

Check wiring and sensor. If this error persists, replace I/O Module. Contact ABB technical support 234881037 E3: I/O-Bus, Mod. 1-10, 0, 0-15
2 0..7

Module 2:

Channel readback error

Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. E3: I/O-Bus, Mod. 1..10, 2, 0..8
3 14 1..10 0 0..15 18 Channel test error Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O Module 234881042 E3: I/O-Bus, Mod. 1-10, 0, 0-15
3 14 1..10 0 0..15 25 Channel stuck - at error Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. 234881049 E3: I/O-Bus, Mod. 1..10, 0, 0..15
3 14 1..10 0 0..15 28 Channel cross-talk error Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O Module 234881052 E3: I/O-Bus, Mod. 1-10, 0, 0-15
3 14 1..10 1 0..3 4 Measurement overflow at the I/O Module Check channel wiring and sensor power supply 234881028 E4: I/O-Bus, Mod. 1..10, 1, 0..3
3 14 1..10 1 0..3 7 Measurement underflow at the I/O Module Check channel wiring and sensor power supply 234881031 E3: I/O-Bus, Mod. 1..10, 1, 0..3
3 14 1..10 1 0..3 45 Cut wire Check channel wiring and sensor power supply 234881069 E3: I/O-Bus, Mod. 1, 1, 1 - 3
3 14 1..10 1 0..3 51 Overload Check channel wiring and sensor power supply 234881075 E3: I/O-Bus, Mod. 1, 1, 1 - 3
3 14 1..10 1 0..3 55 Channel value difference too high Adjust tolerance window for channels. Check channel wiring and sensor configuration. 234881079 E3: I/O-Bus, Mod. 1, 1, 1 - 3
3 14 1..10 2 0..7 18 Channel cross-talk error Check I/O Module wiring. Restart I/O Module, if needed. If this error persists, replace I/O Module. 234881042 E3: I/O-Bus, Mod. 1..10, 4, 0..8
3 14 1..10 2 0..8 43 Internal error Contact ABB technical support. Replace I/O Module. 234881067 E3: I/O-Bus, Mod. 1, 4, 0-7
3 14 1..10 4 0..7 13 Channel test error Check I/O module wiring. Restart I/O Module, if needed. If this error persists, replace I/O module 234881037 E3: I/O-Bus, Mod. 1, 4, 0-7
3 14 1..10 4 0..7 17 Channel test error Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O Module 234881025 E3: I/O-Bus, Mod. 1, 4, 0-7

Remarks:

1)

AC500 uses the following interface identification:

14 = I/O Bus, 11 = COM1 (e.g., CS31 Bus), 12 = COM2

FBP diagnosis blocks do not contain this identifier.

2)

The assignment for “Device” is as follows:

31 = Module, 1..10 = Expansion 1..10

3)

The assignment for “Module” is as follows:

31 = Module or module type (1=AI, 2=DO, 3=AO, 4=DC)

4) In case of module errors, “31 = Module” is reported for the channel.
5) In the current AC500 CPU firmware version, errors reported to the AC500 CPU by the DC505-FBP cannot be directly made visible on the display or in the PLC Browser of the Control Builder PS501.