ModuleDiffBlock Error¶
As of Automation_Builder 2.1.1 the user can read diagnosis information about modules below any PROFINET IO device (e.g. CI50x or CM589).
If a modular PNIO device detects an issue with one of its modules, like plugged module does not match configuration, it reports a ModuleDiffBlock error.
Example
Double-click the node CM589_PNIO_4_Device and open view Diagnosis for PROFINET slave.
- ⇒
In the section Node state appears Node inactive and in the section Node data the Diagnosis state >The IO-Device reported a ModuleDiffBlock…during…<.
Right-click the node CM589_PNIO_4_Device and click Check modules
- ⇒
A popup-window appears.
It shows a list of all modules that are different from the current configuration.
The list contains the slot number(s) of the erroneous module so that a user knows which module(s) causes the issue.
Note
The related context menu item Check modules is visible in online mode of V2 PLCs only.
Note
Automation_Builder does not show the popup-window in case of no differences.
In any case the Automation_Builder adds a message with the result in the message window.