Parameterization

Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…10

Name Value Internal value Internal value, type Default EDS Slot / Index
Module ID 1) Internal 1815 WORD 1815 0x0Y01
Ignore module Internal

Yes

No

BYTE No  
Parameter length Internal 8 BYTE 8 0xY02
Check supply off 0 BYTE 1 0xY03
on 1
Fast counter 3)

0

:

10 2)

0

:

10

BYTE 0 Not for FBP
Behavior outputs at comm. error 5)

Off Last value Last value 5 s Last value 10 s Substitute value

Substitute value 5 s

Substitute value 10 s

0

1 6

11

2

7

12

BYTE

Off

0x00

0x0Y07
*2) Setting Description
  On Error-LED lights up at errors of all error classes, Failsafe mode off
  Off by E4 Error LED lights up at errors of error classes E1, E2 and E3, Failsafe mode off
  Off by E3 Error LED lights up at errors of error classes E1 and E2, Failsafe mode off
  On +Failsafe Error-LED lights up at errors of all error classes, Failsafe mode on*
  Off by E4 + Failsafe Error LED lights up at errors of error classes E1, E2 and E3, Failsafe mode on*
  Off by E3 + Failsafe Error LED lights up at errors of error classes E1 and E2, Failsafe mode on*

1) With a faulty ID, the module reports a “parameter error” and does not perform cyclic process data transmission

2) For a description of the counter operating modes, please refer to the Fast Counter section Fast Counter

3) With CS31 without the parameter “Fast Counter”

Note

The fast counter of the module does not work if the module is connected to a CS31 bus module.

5) The parameter Behavior outputs at comm. error is only analyzed if the Failsafe mode is ON.