Technical Data

The System Data of AC500-eCo apply System Data AC500-eCo

Only additional details are therefore documented below.

Parameter Value
Digital inputs 4 inputs (2 per axis) 24 V DC, can be used as source inputs or as sink inputs
Input channels 0 and 2 Input signal used for axis enable and limit switch
Input channels 1 and 3 Stop, configurable
Input data length 32 bytes
Pulse outputs

Pulse specification

  • 2 outputs for each axis, configurable
  • Type: RS-422 differential signal
  • Mode: CW & CCW or Pulse & Direction
  • Frequency: 10 Hz to 250kHz
  • Pulse number: -2147483648 to 2147483647 (32 bits)
  • Motion profiles generator
Output data lenth 32 bytes
LED displays For power supply, errors and signal states
Internal power supply Via I/O bus
External power supply Via the terminals ZP and UP (process voltage 24 V DC)
Process supply voltage UP Value
Connections Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V)
Rated value 24 V DC
Current consumption via UP terminal 42 mA
Max. ripple 5 %
Inrush current from UP (at power up) 0.067 A²s
Protection against reversed voltage Yes
Rated protection fuse for UP Not necessary
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/bus module Ca. 5 mA
Galvanic isolation Yes, between input groups and the output group and the rest of the module
Isolated groups 5 groups (2 groups for 4 input channels, 1 group for 4 pulse train output channels, 1 group for process supply voltage, 1 group for the rest of the module)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 1.2 W
Weight Ca. 125 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.