Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Parameter Value
Process supply voltage UP  
  Connections Terminals 1.8 for +24 V (UP) and 1.9 for 0 V (ZP)
  Rated value 24 V DC
  Max. ripple 5 %
  Absolute limits at XC version Above 60 °C: 20 VDC … 30 VDC
  Protection against reversed voltage Yes
  Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption  
  From 24 VDC power supply at the Terminal Base of the CPU 10 mA
  Current consumption from UP at normal operation / with outputs 10 mA + 5 mA per input
  Inrush current from UP (at power up) 0,002 A²s
Max. power dissipation within the module 6 W (outputs unloaded)
Max. power dissipation within the module On request
Weight (without terminal block) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load reduced to 50 % at 40°C per group)
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.
Altitude > 2000 m: On request

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.