Technical data of the digital inputs/outputs if \ used as outputs¶
| Parameter | Value |
|---|---|
| Number of channels per module | Max. 8 transistor outputs |
| Common power supply voltage | For all outputs: terminal 1.8 (plus pole of the process supply voltage, signal name UP) |
| Output voltage for signal 1 | UP (-0.8 V) |
| Output delay (0 -> 1 or 1 -> 0) | Typ. 10 µs |
| Output current | |
| Rated value, per channel | 500 mA at UP = 24 V |
| Maximum value (all channels together) | 8 A |
| Leakage current with signal 0 | < 0.5 mA |
| Rated protection fuse for UP | 10 A fast |
| De-magnitization when inductive loads are switched off | With varistors integrated in the module (see figure below) |
| Switching frequency | |
| With resistive load | On request |
| With inductive loads | Max. 0.5 Hz |
| With lamp loads | Max. 11 Hz with max. 5 W |
| Short-circuit proof / overload proof | Yes |
| Overload message (I > 0.7 A) | Yes, after ca. 100 ms |
| Output current limitation | Yes, automatic reactivation after short-circuit/overload |
| Resistance to feedback against 24 V signals | Yes |
| Max. cable length | |
| Shielded | 1000 m |
| Unshielded | 600 m |
The following drawing shows the circuitry of a digital input/output with the varistors for demagnetization when inductive loads are switched off.