Technical data of the digital inputs/outputs if used as inputs

Parameter Value
Number of channels per module Max. 8 digital inputs
Reference potential for all inputs Terminal 1.9 (negative pole of the process supply voltage, signal name ZP)
Input current per channel  
Input voltage +24 V Typ. 5 mA
Input voltage +5 V > 1 mA
Input voltage +15 V > 5 mA
Input voltage +30 V < 8 mA
Input type acc. to EN 61131-2 Type 1
Input delay (0 -> 1 or 1 -> 0) Typ. 2 µs
Input signal voltage 24 VDC
Signal 0 -3 V…+5 V *
Undefined signal > +5 V…< +15 V
Signal 1 +15 V…+30 V
Ripple with signal 0 Within -3 V…+5 V *
Ripple with signal 1 Within +15 V…+30 V
Max. cable length  
Shielded 1000 m
Unshielded 600 m

*  Due to the direct connection to the output, the demagnetizing varistor is also effective at the input (see figure) above. This is why the difference between UPx and the input signal must not exceed the clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V. Consequently, the input voltage must range from - 12 V to + 30 V when UPx = 24 V and from - 6 V to + 30 V when UPx = 30 V.