I/O / Process Data and Diagnosis Section (Cyclic Data)

The cyclic data section for CI52x-MODTCP

Register (hex) Description Readable by MODBUS function code Writeable by MODBUS function code
FCE *) Module state 3,4, 23 x
FFA Diagnosis 3,4, 23 x
1000 Inputs CI 3, 4, 23 x
1100 Inputs 1.EXP 3, 4, 23 x
… …   x
1A00 Inputs 10.EXP 3, 4, 23 x
2000 Outputs CI 3, 23 6, 16, 23
2100 Outputs 1.EXP 3, 23 6, 16, 23
… …    
2A00 Outputs 10.EXP 3, 23 6, 16, 23
2B00 Dummy output 3, 23 6, 16, 23

*) supported from CI52x firmware version V3.2.0 (device index F0)

This section can be divided again in three sections:

  • Module state (containing the state of connected expansion modules and hot swap terminal units)
  • Diagnosis data (containing diagnosis data in AC500 specific format)
  • Process data (containing I/O data)