Technical DataΒΆ
The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.
| Process supply voltage L+ | ||
| Connections | Terminal 19 for L+ (+24 V DC) and terminal 20 for M (0 V) | |
| Rated value | 24 V DC | |
| Current consumption via L+ terminal | 0.14 A + output load | |
| Inrush current (at power-up) | 0.05 A s |
|
| Max. ripple | 5 % | |
| Protection against reversed voltage | Yes | |
| Protection fuse for L+ | Recommended | |
| Current consumption from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | Ca. 5 mA | |
| Electrical isolation | No | |
| Surge-voltage (max.) | 35 V DC for 0.5 s | |
| Max. power dissipation within the module | On Request | |
| Weight | ca. 120 g | |
| Mounting position | Horizontal or vertical | |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | |