TA541 - Lithium Battery

  • Manganese dioxide lithium button cell, 3 V, 560 mAh
  • Primary cell, non-rechargeable
../_images/50187e654280478c0a33139008f41d2d1

Lithium Battery TA541

Purpose

The TA541 lithium battery is the only applicable battery for PM595 PM595. It is used to save RAM content of the Processor Module (PM595-4ETH-F only) and to back-up the real-time clock (all PM595 variants). It is a primary cell and cannot be re-charged.

The Processor Modules are supplied without a lithium battery. It therefore must be ordered separately. The TA521 Lithium Battery is used to save RAM contents of AC500 Processor Modules and back-up the real-time clock. Although the Processor Modules can work without a battery, its use is still recommended in order to avoid process data being lost.

The CPU monitors the discharge degree of the battery. A warning is output, before the battery condition becomes critical (about 2 weeks before). After the warning message has appeared, the battery should be replaced as soon as possible.

Handling Instructions

  • Do not short-circuit or re-charge the battery! It can cause excessive heating and explosion.
  • Do not disassemble the battery!
  • Do not heat up the battery and not put into fire! Risk of explosion.
  • Store the battery in a dry place.
  • Replace the battery with supply voltage ON in order not to risk data being lost.
  • Recycle exhausted batteries meeting the environmental standards.
../_images/9e53f3b0e38789ee0a331390015ea5a71

Battery Lifetime

The battery lifetime is the time the battery can store data while the CPU is not powered. As long as the CPU is powered, the battery will only be discharged by its own leakage current.

Technical Data

The System Data of AC500 and S500 System Data AC500 are valid here. Only additional details are therefore documented below.

Nominal voltage 3 V
Nominal capacity 1800 mAh
Temperature range

Operating: -40 °C … 70 °C

Storage: -40 °C … +85 °C

Transport: -40 °C … +85 °C

Battery lifetime Typ. 3 years at 25 °C
Self-discharge

1 % per year at 25 °C

5 % per year at 40 °C

20 % per year at 60 °C

Protection against reverse polarity Yes, by mechanical coding of the plug
Insulation The battery is completely insulated.
Connection Red = plus pole = above at plug, black = minus pole,
Weight 17 g
Dimensions

Diameter of the cell: 18 mm,

Height of the cell: 34.5 mm

Ordering Data

Order No. Scope of delivery
1SAP 182 700 R0001 TA541, lithium battery