Properties

41db97311aa887edc0a8640e0066b403_f7411f87f69cefcbc0a8640e002e0094 : In the Properties section of the Configuration tab the following functions can be performed dependent on the marked object or the marked instance:

Note

If you move the mouse pointer over an input field or the name of an input field, you get a tooltip with a description in the window below the Properties (see the following figure).

Parametrization of the IEC 61850 Server

../_images/4c60e79305fc1c2bc0a8640e0022b642

‘Properties’ with tooltip of ‘Max. client count’

Property Description
Server Name Name of the server,
IP I Subnetmask I Gateway Own IED IP address, I Subnetmask I own gateway address
Max.client count The maximum number of clients that can connect to the IED, possible values: 1, 2, 3, 4, 5
Allowed IPs

Allowed IPs for clients 1…5

default is 0.0.0.0, whereby an IP address that equals 0.0.0.0 means that no IP address validity test will take place. If more than one client connection was selected above, additional IPs must be configured for each one. As soon as an IP address is parameterized with 0.0.0.0, testing for all connected clients is deactivated.

Time synchronisation

Selection: SNTP

SNTP (default): SNTP time synchronization. In addition to activation, functionality must be parameterized in the device’s web-based management. Currently, the SNTP time telegram does not use milliseconds, which means accuracy is measured in 1 second increments.

1. Input field Time zone: Offset between Greenwich (GMT)- and the local time (for Germany 1 h, for example). The value is limited between -12 an d+ 14

2. Input field: DLS Mode: Ratio for the mode summer/winter time changeover. Possible values:

  • 0 = No automatic summertime/wintertime changeover
  • 1 = Timeover from wintertime to summertime on last the Sunday in March, changeover from summertime to wintertime on the last Sunday in October
Task Prio I Interval

Task

1.input field: entry of the priority,

2.input field: entry of the interval in ms

TCP KeepAlive[sec] The KeepAlive is to check the connection to the client.

Entry of a device name for the Logical Device

If the Logical Device 41db97311aa887edc0a8640e0066b403_f8d21807052873f7c0a8640e0159ead5 is focused in the configured server you can entry a device name for the Logical Device in the ‘Properties’ section.

Connecting an attribute (DA) with a CODESYS variable

  1. Select the attribute of a CDC instance below the server.

  2. Enter the desired CODESYS variable name into the input field Monitoring Var in the properties section.

    Entry optionally an initial value into the input field right-side hand of the variable name.

In case of an attribute with RW-access, a Control Variable (writing access) can be entered in addition to the Monitoring Var variable (reading access) . For a more detailed description about reading and writing of variables at the IEC 61850 Server see Reading and Writing from CODESYS Variables. The monitoring and control variables declared in the Properties section are displayed next to the respective attribute and at the superordinated node DO of the server tree.

By activating the Autom. declare checkbox the variable is declared by the IEC 61850 configurator and stored in the IEC61850_Generated_GVL (of the IEC61850 Generated POUs folder) after Generate code of the IEC 61850 Server.

Note

If you do not activate the Autom. declare checkbox you select the variable via the input assistance (F2)) or you declare the variable yourself.

Trigger option: With the trigger options you set the attributes to select the events which might trigger a report. The selected trigger option is displayed in the status bar. For a description of the options see Status bar.

Note

The trigger option determines whether the Report, assigned to the DataSet, is sent when the value of this attribute changes.

../_images/ab08eaeb19c3db1ac0a8640e00bc9724

‘Properties’ for the attribute(DA) ‘ctlNum’, input fields: ‘Monitoring Var’ with ‘Initvalue’

../_images/b38435920aca088bc0a8640e01149c6a

‘Properties’ of an attribute with RW-access: in addition input : ‘Control Variable’

Entry of a node prefix for LNC instances

../_images/7c26ef9a1a8d83f9c0a8640e00917ef8

‘Properties’ of the LNC instance ‘GGIO1’ with ‘Node prefix’ input field

Here you enter a prefix for the selected LNC instance. The prefix is put in front of the LN name in the server tree. The prefix is displayed in the Status bar, too.