Output Description

../_images/2e868859e38acae30a33139000eba54e

DONE

Data_Type Default_Value Range Unit
BOOL - TRUE / FALSE -

Output DONE indicates the state of execution.

It has the value TRUE when the execution is finished and the outputs are valid. When DONE becomes FALSE other outputs are not valid any more.

ERR

Data_Type Default_Value Range Unit
BOOL - TRUE / FALSE -

Output ERR indicates whether an error occurred during Function Block execution.

It is only valid when DONE is TRUE. The kind of occurred error is specified by the error identifier at output ERNO.

ERNO

Data_Type Default_Value Range Unit
WORD - 0 … 65535 -

At output ERNO the identifier of an occurred error is provided. It is only valid when DONE and ERR is TRUE (see, error messages): Error Messages of the Function Block Libraries

IN0…IN7

Data_Type Default_Value Range Unit
BOOL - - -

The outputs IN0…IN7 display which inputs triggered an interrupt since the last Function Block calling. 4 channels (I0..I3) of AC500-eCo Onboard I/O can be configured as interrupt inputs. Therefore, IN0…IN3 will be used to display the status of interrupt inputs.

LOST

Data_Type Default_Value Range Unit
BOOL - - -

If interrupt pulse was lost, LOST=TRUE. Otherwise, LOST=FALSE.