2000hex…2FFFhex - Interface Error

DEC HEX Error description
8193 2001

Invalid interface, Communication Module number or slot ID

COM: Interface is not configured in the “free mode”

HA: Wrong COM number at input COM

ETH-MOD-MAST: Invalid interface or slot ID

8194 2002 Command not supported by the interface. The function is not supported by the device firmware. Block library newer than the device firmware.
8195 2003 Invalid interface or Communication Module type. Block is not suitable for this type.
8197 2005 HA..: CS31 Bus failure
8198 2006 Fault on both local and remote CPU.
8211 2013

Timeout

COM_MOD_MAST: Slave did not respond within the specified time

HA..: No ETHERNET link, Error in DPRAM communication between CM574-RS and PM5xx.

8212 2014 Framing error (incorrect baud rate, number of stop bits and/or bits per character)
8213 2015

Parity error

HA: Remote CS31 slave sync error. Difference in digital/ analog output buffer of PLC A and B

8214 2016

Idle error

COM..: Character timeout occurred

8215 2017

Invalid length

COM_MOD_MAST: Invalid data length received

COM_REC: Received more data than expected

8216 2018 Checksum error
8217 2019 Handshake error
8218 201A

Service failed

COM_REC: Unknown error message of the interface

COM_SET_PROT: Interface hardware not accessible. Initialization already failed during system start-up.

COM_MOD_SLV_SET_ADDR..: Internal error (e.g. wrong return value of internal function, null pointer received)

CS31..: Internal error (e.g. CS31 communication failed)

FC..: Internal error (e.g. null pointer received, wrong return value of internal function, no entry in config found)

HA..: Internal error (e.g. null pointer received, wrong return value of internal function, no entry in configuration found)

8219 201B

Access error

HA..: Remote CS31 Bus failure: Other CPUs’ CS31 Bus is out of order

IO..: Module number does not exist

8220 201C

Incorrect number (quantity)

COM_SET_PROT: Invalid protocol index. Index is not supported by the device firmware.

COM_MOD_SLV_SET_ADDR..: Invalid protocol index.

HA..: Numbers of CI590-CS31-HA devices configured in line A and line B are different

IO..: Invalid module number

8223 201F

Access denied

COM..: Access to the interface is not possible at present. Control Builder, OPC or another program is logged in via the interface.

8226 2022

COM_MOD_SLV_SET_ADDR..: Wrong configuration (No protocols configured).

FC..: Wrong configuration (e.g. no ABB Control Builder Plus configuration, no CS31 configured, no CS31 modules found).

HA..: Overflow of HA_DATA reference table

8233 2029
  • HA_CS31_CONTROL:
    • CI590-CS31-HA Slave configuration not complete
    • CI590-CS31-HA Slaves in Bus1 and Bus2 are mix-wired
    • Remote CI590-CS31-HA Failure
    • CS31 Master Cross Wired / No CS31 configuration / No submodules on CS31 bus
  • HA_CS31_DIAG/ HA_CS31_DIAG_VIA_CM574-RS
    • CI590-CS31-HA slaves in line A and line B are mix-wired.
8234 202A

HA: Configuration error:

  • Wrong CM574-RS communication
  • CM574-RS COM interface is not configured for shared communication
  • CM574-RS not added to Communication Module slot
  • Wrong configuration of DIAG blocks