PUMP_ ANTIJAM _VISU_PH

Visualization Faceplate for the Function Block PUMP_ ANTIJAM.

../_images/3582a7f48bb1bdc30a3313905265b2c4

Visualization in offline mode.

../_images/2feb38198bb1c36d0a331390107d3dd6

Visualization in online mode.

Colors of the variables
Color Meaning
white Actual FALSE and should be FALSE in normal operation
green Actual TRUE and should be TRUE in normal operation
yellow Actual FALSE but should be TRUE in normal operation
red Actual TRUE but should be FALSE in normal operation
Visualization parameters
Variable element Access Way of access Description (all elements refer to the Function Block instance, replaced for the placeholder $FB$)
EN R/W Toggle To enable the Function Block with the true value.
PUMP_ID R/W Numpad- value 1 to 3 To enter the ID of the pump which is to be cleaned
TRIGGER R/W Numpad- value 0 to 4 Trigger to clean the pump. 0=not enabled, 1=master enabled, 2=follower enabled, 3=at start, 4=manual mode
FWD_REF_SPEED R/W Numpad- value 0 onwards Speed reference to clean the pump in the forward direction
BWD_REF_SPEED R/W Numpad- value 0 onwards Speed reference to clean the pump in the backward direction
OFF_TIME R/W Numpad- value 0 onwards Time delay in seconds between the forward and the backward movement in anti-jam
FWD_STEP_TIME R/W Numpad- value 0 onwards Time duration in seconds for which the pump moves in the forward direction in anti-jam
BWD_STEP_TIME R/W Numpad- value 0 onwards Time duration in seconds for which the pump moves in the reverse direction in anti-jam
ANTIJAM_STEPS R/W Numpad- value 1 onwards Number of steps to be performed in an anti-jam process
ALLOW_REVERSE R/W Toggle True value means the pump can also move in the reverse direction to perform the anti jam
START_MANUAL R/W Toggle For the TRUE anti-jam is performed in the manual mode i.e. TRIGGER =4
DONE R   Execution finished when output DONE = TRUE.
ERR R   Error occurred during execution when output ERR = TRUE.
ENO R   Error code.