PUMP_ ANTIJAM _VISU_PH
Visualization Faceplate for the Function Block PUMP_ ANTIJAM.
Colors of the variables
Color |
Meaning |
white |
Actual FALSE and should be FALSE in normal operation |
green |
Actual TRUE and should be TRUE in normal operation |
yellow |
Actual FALSE but should be TRUE in normal operation |
red |
Actual TRUE but should be FALSE in normal operation |
Visualization parameters
Variable element |
Access |
Way of access |
Description (all elements refer to the Function Block instance, replaced for the placeholder $FB$) |
EN |
R/W |
Toggle |
To enable the Function Block with the true value. |
PUMP_ID |
R/W |
Numpad- value 1 to 3 |
To enter the ID of the pump which is to be cleaned |
TRIGGER |
R/W |
Numpad- value 0 to 4 |
Trigger to clean the pump. 0=not enabled, 1=master enabled, 2=follower enabled, 3=at start, 4=manual mode |
FWD_REF_SPEED |
R/W |
Numpad- value 0 onwards |
Speed reference to clean the pump in the forward direction |
BWD_REF_SPEED |
R/W |
Numpad- value 0 onwards |
Speed reference to clean the pump in the backward direction |
OFF_TIME |
R/W |
Numpad- value 0 onwards |
Time delay in seconds between the forward and the backward movement in anti-jam |
FWD_STEP_TIME |
R/W |
Numpad- value 0 onwards |
Time duration in seconds for which the pump moves in the forward direction in anti-jam |
BWD_STEP_TIME |
R/W |
Numpad- value 0 onwards |
Time duration in seconds for which the pump moves in the reverse direction in anti-jam |
ANTIJAM_STEPS |
R/W |
Numpad- value 1 onwards |
Number of steps to be performed in an anti-jam process |
ALLOW_REVERSE |
R/W |
Toggle |
True value means the pump can also move in the reverse direction to perform the anti jam |
START_MANUAL |
R/W |
Toggle |
For the TRUE anti-jam is performed in the manual mode i.e. TRIGGER =4 |
DONE |
R |
|
Execution finished when output DONE = TRUE. |
ERR |
R |
|
Error occurred during execution when output ERR = TRUE. |
ENO |
R |
|
Error code. |