PUMP_ FLOW_CALC_VISU_PH

Visualization Faceplate for the Function Block PUMP_ FLOW_CALC.

../_images/c43dbc2f12614b3d0a331390005959aa
Colors of the variables
Color Meaning
white Actual FALSE and should be FALSE in normal operation
green Actual TRUE and should be TRUE in normal operation
yellow Actual FALSE but should be TRUE in normal operation
red Actual TRUE but should be FALSE in normal operation
Visualization parameters
Variable element Access Way of access Description (all elements refer to the Function Block instance, replaced for the placeholder $FB$)
EN R/W Toggle To enable the Function Block with the true value.
PUMP_ID R/W Numpad- value 1 to 3 To enter the ID of the pump which is to be cleaned.
PQ_CURVE_P1 R/W Numpad- value 0 onwards Pump PQ curve P1.
PQ_CURVE_Q1 R/W Numpad- value 0 onwards Pump PQ curve Q1.
PQ_CURVE_P2 R/W Numpad- value 0 onwards Pump PQ curve P2.
PQ_CURVE_Q2 R/W Numpad- value 0 onwards Pump PQ curve Q2.
PQ_CURVE_P3 R/W Numpad- value 0 onwards Pump PQ curve P3.
PQ_CURVE_Q3 R/W Numpad- value 0 onwards Pump PQ curve Q3.
PQ_CURVE_P4 R/W Numpad- value 0 onwards Pump PQ curve P4.
PQ_CURVE_Q4 R/W Numpad- value 0 onwards Pump PQ curve Q4.
PQ_CURVE_P5 R/W Numpad- value 0 onwards Pump PQ curve P5.
PQ_CURVE_Q5 R/W Numpad- value 0 onwards Pump PQ curve Q5.
NOMINAL_POWER   Numpad- value 0 onwards Nominal power of the motor in kW.
ACT_SPEED R   Actual speed of the motor in RPM is connected to the input.
ACT_POWER R   Actual power of the motor in kW.
PUMP_MOTOR_EFF     Combined efficiency of the motor and the pump set.
LOW_SPEED_CALC     Speed below which the calculation will not take place.
DONE R   Execution finished when output DONE = TRUE.
ERR R   Error occurred during execution when output ERR = TRUE.
ENO R   Error code.
ACT_FLOW R   Calculated flow of the pump.