PUMP_ AUTOCHANGE _VISU_PH
Visualization Faceplate for the Function Block PUMP_ AUTOCHANGE.
Colors of the variables
Color |
Meaning |
white |
Actual FALSE and should be FALSE in normal operation |
green |
Actual TRUE and should be TRUE in normal operation |
yellow |
Actual FALSE but should be TRUE in normal operation |
red |
Actual TRUE but should be FALSE in normal operation |
Visualization parameters
Variable element |
Access |
Way of access |
Description (all elements refer to the Function Block instance, replaced for the placeholder $FB$) |
EN |
R/W |
Toggle |
To enable the Function Block with the true value. |
AUTOCHG_STYLE |
R/W |
Numpad- value 0 to 3 |
Mode of auto change. 0=None, 1=fixed, 2=runtime difference, 3=all stop. |
AUTOCHG_INTERVAL |
R/W |
Numpad- value 0 onwards |
Time delay after which the autochange starts when AUTOCHG_STYLE =1. |
RUNTIME_DIFFERENCE |
R/W |
Numpad- value 0 onwards |
Maximum permited runtime difference between the two pumps after which the autochange starts when AUTOCHG_STYLE =2. |
DONE |
R |
|
Execution finished when output DONE = TRUE. |
ERR |
R |
|
Error occurred during execution when output ERR = TRUE. |
ENO |
R |
|
Error code. |