PUMP_ AUTOCHANGE _VISU_PH

Visualization Faceplate for the Function Block PUMP_ AUTOCHANGE.

../_images/bee551d612613cca0a33139000e36a10
Colors of the variables
Color Meaning
white Actual FALSE and should be FALSE in normal operation
green Actual TRUE and should be TRUE in normal operation
yellow Actual FALSE but should be TRUE in normal operation
red Actual TRUE but should be FALSE in normal operation
Visualization parameters
Variable element Access Way of access Description (all elements refer to the Function Block instance, replaced for the placeholder $FB$)
EN R/W Toggle To enable the Function Block with the true value.
AUTOCHG_STYLE R/W Numpad- value 0 to 3 Mode of auto change. 0=None, 1=fixed, 2=runtime difference, 3=all stop.
AUTOCHG_INTERVAL R/W Numpad- value 0 onwards Time delay after which the autochange starts when AUTOCHG_STYLE =1.
RUNTIME_DIFFERENCE R/W Numpad- value 0 onwards Maximum permited runtime difference between the two pumps after which the autochange starts when AUTOCHG_STYLE =2.
DONE R   Execution finished when output DONE = TRUE.
ERR R   Error occurred during execution when output ERR = TRUE.
ENO R   Error code.