Connection of sensors to the 5-V-power-supplyΒΆ

The following figure shows the electrical connection of sensors to the 5-V-power-supply 0 of the module CD522. Proceed with the 5-V-power-supply 1 in the same way.

Note

Each 5-V-power supply provides a current of 100 mA max. It is possible to parallel both integrated power supply. In this case, the max. current is 200 mA.

../_images/aedc38b894d2c4e10a3313904267b8361

Connection of sensors to the 5-V-power supply of the module CD522

Attention

:strong:Risk of damaging the CD522!

The integrated 2-A-fuse cannot be replaced. If it blows, the module must be replaced.

Ensure that the current per 0-V-connection does not exceed 0.5 A.

Attention

:strong:Risk of damaging the CD522!

The two 5-V-outputs have no protection against reverse polarity.

The meaning of the LEDs is described in the Displays Encoder & PWM Module CD522.