Connection and Wiring

For detailed information such as technical data of your mounted devices (AC500 product family) refer to the hardware device description of the appropriate device AC500 Device Description (Hardware).

Attention

:strong:Attention:

The devices should be installed by trained persons with knowledge of wiring electronic devices. In case of bad wiring, the following problems could occur:

  • On the Terminal Base, the terminals L+ and M are doubled. If the power supply is badly connected, a short circuit could happen and lead to a destruction of the power supply or its fuse. If no suitable fuse exists, the Terminal Base itself could be destroyed.
  • The Terminal Bases and all electronic modules and Terminal Units are protected against reverse polarity.
  • All necessary measures should be carried out to avoid damages to modules and wiring. Notice the wiring plans and connection examples.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.